Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1026-01704
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2026 | Commercial Building | APPROVED | |||
| 10/27/2026 | Site Zoning | APPROVED | |||
| 10/29/2026 | Water - PDSD | APPROVED | |||
| 10/21/2026 | Site Engineering | NOT REQUIRED | |||
| 10/28/2026 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1026-01704 (2530 N CAMPBELL AV TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov 1. Provide GFCI protection for the clothes dryer per NEC 210.8(D)(11). Readily accessible per NEC 210.8, may require GFCI breakers for both the washer and the dryer. |
||
| 11/02/2026 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide the specifications and sequence of operation for EF-1. Reference: Section 107.2.1, IBC 2024. 2. Footnote b on Table 403.3.1.1, IMC 2024 states that mechanical exhaust is required for the nail salon and no air from the nail salon may be recirculated from the nail salon to any other space. HP-B appears to be recirculating air to the laundry and restroom. Reference: Section 403.2.1 (3), IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov. |
||
| 11/02/2026 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The title for detail 206/P2 refers to the installation of a reduced pressure backflow preventer (RPBP) but the detail indicates that a pressure vacuum breaker (Watts LF008PCQT). Clarify which type of backflow preventer is to be installed and if it is the pressure vacuum breaker, specify the minimum mounting height. 2. The hot water supply to the pedicure chairs exceeds the maximum piping length allowed by Section C404.5, IECC 2024 for 1-inch hot water supply pipe (i.e.13 feet). If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 11/04/2026 | Fire New Construction | REVIEW COMPLETED | |||
| 10/21/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |