Permit Review Detail
Review Status: In Review
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1026-01695
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2026 | Commercial Electrical Standard | APPROVED | |||
| 11/05/2026 | Commercial Plumbing Standard | APPROVED | |||
| 10/20/2026 | Site Engineering Standard | APPROVED | |||
| 11/06/2026 | Site Zoning Standard | APPROVED | |||
| 11/02/2026 | Outdoor Lighting Standard | NOT REQUIRED | No modifications to the outdoor lighting. | ||
| 11/05/2026 | Water - PDSD Standard | NOT REQUIRED | |||
| N/A | Commercial Building Standard | PENDING ASSIGNMENT | |||
| N/A | Commercial Post Review Express | PENDING ASSIGNMENT | |||
| N/A | Fire New Construction Standard | PENDING ASSIGNMENT | |||
| 11/05/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | 1. Ventilation is required and must be provided whenever the space is occupied. Provide ventilation calculations and show how the ventilation will be provided. Reference: Sections 401.2 and 401.3, IMC 2024. 2. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.9, IMC 2024. If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov |
||
| 10/20/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |