Permit Number: TC-COM-1026-01695
Parcel: 140442500

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01695
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2026 Commercial Electrical Standard APPROVED
11/05/2026 Commercial Plumbing Standard APPROVED
10/20/2026 Site Engineering Standard APPROVED
11/06/2026 Site Zoning Standard APPROVED
11/02/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
11/05/2026 Water - PDSD Standard NOT REQUIRED
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Commercial Post Review Express PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
11/05/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Ventilation is required and must be provided whenever the space is occupied. Provide ventilation calculations and show how the ventilation will be provided. Reference: Sections 401.2 and 401.3, IMC 2024.
2. Secure the refrigerant circuit access ports of the condensing units to prevent unauthorized access. Reference: Section 1101.9, IMC 2024.

If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
10/20/2026 PDSD Application Completeness Express REVIEW COMPLETED