Permit Number: TC-COM-1026-01665
Parcel: 10408051D

Address:
4565 N ORACLE RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01665
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2026 Commercial Building APPROVED
10/15/2026 Site Engineering APPROVED
10/23/2026 Site Zoning APPROVED
10/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/19/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical review TC-COM-1026-01665 (4565 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide a Grounding Electrode System at the detached structure per 250.31(A), 690.47. Grounding electrode system and grounding electrode conductor. Required.
2. Provide appropriate grounding and bonding of all metal structures, per all relevant sections of NEC 250 (example sections 250.4(A), 250.20, 250,32, 250.104, 690.43.
10/19/2026 Outdoor Lighting REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1026-01665 (4565 N ORACLE RD TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Show new under-canopy lighting fixtures with a Maximum color temperature, 3500K, OLC 402.1.
2. Show new under-canopy lighting fixtures as full-cutoff/fully-shielded per OLC chapter 2 definition or provide complete site lumen calculations and compliance with the outdoor lighting code. OLC 401.2.1(3).
10/28/2026 Fire New Construction REVIEW COMPLETED
10/14/2026 PDSD Application Completeness Express REVIEW COMPLETED