Permit Number: TC-COM-1026-01660
Parcel: 11204375A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01660
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2026 Site Engineering APPROVED FPU Created - TE-FPU-1026-00422
10/21/2026 Site Zoning APPROVED
10/22/2026 Commercial Mechanical NOT REQUIRED
10/22/2026 Commercial Plumbing NOT REQUIRED
10/27/2026 Fire New Construction NOT REQUIRED
10/22/2026 Water - PDSD NOT REQUIRED
10/27/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/26/2026 Commercial Building REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1026-01660
ADDRESS/PARCEL: (2856 E FORT LOWELL RD TUCSON, AZ 85716)

Submit your revised drawings along with a ***detailed response letter***, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.

Should you have any questions about these Commercial Building comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.

COMMENTS:
1. SITE PLAN: Please locate/identify/label/dimension the fire damaged portion of the building wall on the site plan.
2. Please provide a Floor Plan showing the elements of was being repaired. Clearly identify what is being proposed.
3. Please provide drawings of the interior wall and exterior wall illustrating the area being repaired.
4. Please provide detailed drawings that illustrate and correspond to the Fire Inspection Report.
PLEASE ENSURE ALL SUBMITTED DRAWINGS HAVE A SEAL/SIGNATURE/DATE SIGNED BY AN ARIZONA LICENSED ARCHITECT/PROFESSIONAL.
5. Epoxy is proposed for the anchor bolts. Special Inspection will be required.
a. Please provide a special inspection certificate with Part A, and Part B completed with next submittal. Special Inspection(s) Required (Provide table specific to the project) IBC 1705 This form is available in:
b. https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-development-services/documents/special_inspection_certificate.pdf
c. Ensure that Part B is sealed/signed/dated by the special inspector in charge. Ensure to use Special Inspectors who are active in the approved list of special inspectors. They are available in the following links:
d. special-inspectors-by-name.pdf (orovalleyaz.gov)
e. https://content.civicplus.com/api/assets/e426f390-7bd6-4c47-9bc1-357282083afd
f. https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00870.pdf
6. Please resubmit.
10/19/2026 Commercial Electrical REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01660 (2856 E FORT LOWELL RD TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide completed, and sealed electrical sheets ready for construction.
10/13/2026 PDSD Application Completeness Express REVIEW COMPLETED