Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01654
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/23/2026 Commercial Electrical Standard APPROVED Sheet E20 Provide exit sign exit from the patio.
10/23/2026 Commercial Mechanical Standard APPROVED
10/23/2026 Commercial Plumbing Standard APPROVED
10/15/2026 Site Engineering Standard APPROVED
10/28/2026 Site Zoning Standard APPROVED
10/30/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/23/2026 Commercial Building Standard REQUIRES RESUBMIT Willdan Engineering Phoenix
Ed Kulik (480) 241-0634 ekulik@willdan.com

1. Sheet G1.0 Provide an accessible path travel from parking to front entry.
2. Sheet D10 Show details for slab repairs.
10/30/2026 Fire New Construction Standard REQUIRES RESUBMIT -Include the lockset information on door schedule. A2's have different requirements for locking hardware IFC 1010.2.4. Panic hardware required for second exit per IFC 1010.2.8.
john.vincent@tucsonaz.gov
5203495581
10/23/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1026-01654 (6536 E TANQUE VERDE RD Unit:UNIT 140 TUCSON, AZ 85715)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. The reflected ceiling plan on A2.0, and the lighting plan on E2.0 appear to show different lighting fixtures.
3. The string lighting on sheet E2.0, used on the outdoor patio are typically unshielded. Show, by providing the manufacture’s specification sheets, that these lights are full-cutoff and under a canopy, or meet all the requirements below, and provide lumen calculations for the entire site.
4. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different outdoor light sources on your lighting plan, both new and existing. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
5. List the Lighting Area per OLC (typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
6. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
7. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
8. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
9. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type.
10. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

11. Specify any exceptions used.

12. Provide Curfew lighting controls If applicable Per section 403.
10/26/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1026-01654
ADDRESS/PARCEL: 6536 E TANQUE VERDE RD Unit:UNIT 140 TUCSON, AZ 85715

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Please identify the existing water meter size and location, the total water demand served by the meter, and the size and location of the associated backflow prevention assembly. Reference: Section 107.2.1, IBC 2024.
10/09/2026 PDSD Application Completeness Express REVIEW COMPLETED