Permit Number: TC-COM-1026-01638
Parcel: 124051160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1026-01638
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2026 Site Engineering Standard NOT REQUIRED
10/26/2026 Commercial Post Review Express PENDING ASSIGNMENT
10/09/2026 Addressing Validation REQUIRES RESUBMIT If you have any questions about this review, please contact CDRC@tucsonaz.gov

The project address on this permit application does not match the project address on the plans submitted. Please update the plans and resubmit, or, submit a Request Change of Address if the permit application is incorrect.

How to request a change of address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf

Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf
10/22/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1026-01638 (746 E 5TH ST Unit:BLDG 1 TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Provide complete electrical plans for the new flood-lights. These lights were installed between 2017 and 2019 without a permit.
2. Provide an electrical plan showing any/all electrical work. Plans shall include but may not be limited to items below and as necessary for the actual scope of work:
3. Provide an electrical panel schedule and designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1.
4. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.
5. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.

>>> Additional comments may be forthcoming when reviewing updated plans.
10/22/2026 Historic REQUIRES RESUBMIT HISTORIC REVIEW REQUIRED: This property is located within the West University Historic Preservation Zone (HPZ). Minor Historic Review is required.
APPLICATION REQUIREMENTS: Historic Review requires the submittal of a supplemental Design Package. As part of your Design Package, please include the following items combined into a single PDF: project description, site plan showing existing and proposed, elevations showing existing and proposed, lighting specifications/details, photographs of existing conditions (provide photographs of entire facades/each elevation where work is proposed and provide photos of details). If you have product names/specifications/brochures, include that in your Design Package. Also include the Historic Property Inventory Form for the property, which can be accessed here: https://assets.tucsonaz.gov/share/preservation/inventoryforms/WU-745.pdf.
For more information reference the following handout, HISTORIC REVIEW INFORMATION GUIDE: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/historic-preservation/historic-review-information-guide_091726.pdf.
CREATE HISTORIC SUB-RECORD: You will need to create Special Districts-Historic sub-record following these instructions: https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/sub-records.pdf. Once you are ready to submit your Design Package, upload it as a SINGLE COMBINED PDF to your Special District-Historic Sub-Record. The Historic review for your project will be processed and recorded in the Sub-Record.
QUESTIONS: For questions or to set up a meeting with Historic staff, please contact: PDSDHistoric@tucsonaz.gov.
10/22/2026 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1026-01638 (746 E 5TH ST Unit:BLDG 1 TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. The outdoor lighting lumen calculations are incorrect. These are not low-pressure sodium lighting fixtures and thus do not qualify for Option 1, Table 401.1.
2. Per the associated code enforcement case and attached pictures, these lights are not full-cutoff as stated on the Sealed drawings. All lighting fixtures are unshielded.
3. The flood-lights must all be replaced with actual full-cutoff fixtures.
4. Provide the manufacturer’s specification sheets for the outdoor lighting fixtures. Include the lumen and color temperature values for each outdoor fixture type. >>> lighting fixtures must be proven to be full-cutoff.
5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
6. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

8. Specify any exceptions used.

9. Provide Curfew lighting controls If applicable Per section 403.
10/26/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Jeffrey W. Cassidy, Planner I
Planning & Development Services Department – Current Zoning Review Section, Commercial

PROJECT:
TC-COM-1026-01638 – Commercial Building – Add more security lights
746 E 5TH ST Unit BLDG 1 TUCSON, AZ 85719 (HR-3 Zoning)
1st Review

TRANSMITTAL DATE:
October 26, 2026

1. COMMENT: Zoning has completed this review with four comments but cannot ultimately approve until the until the Historic reviewer comments are met and completed (Refer to Historic Reviewer Comments for further direction).

2. COMMENT: Additional comments may be forthcoming on the next review based on responses to Zoning and other PDSD reviewer comments.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:

3. Corrected building permit

4. Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home

Instructions for resubmittal - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/old-pdfs/double-old/resubmittals.pdf

If you have any questions about this transmittal, please contact jeffrey.cassidy@tucsonaz.gov

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code
10/09/2026 PDSD Application Completeness Express REVIEW COMPLETED