Permit Number: TC-COM-1026-01635
Parcel: 12709012E

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1026-01635
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/21/2026 Commercial Electrical APPROVED
10/21/2026 Commercial Mechanical APPROVED
10/21/2026 Commercial Plumbing APPROVED
10/21/2026 Site Zoning APPROVED
10/07/2026 Site Engineering NOT REQUIRED
10/20/2026 Water - PDSD NOT REQUIRED
10/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/21/2026 Commercial Building REQUIRES RESUBMIT October 20, 2026
1st Review

Intertech Architectural Interiors
Attn: Erin Hastreiter
6089 E. Grant Road
Tucson, Arizona 85712

Re: LJA STORAGE ROOM
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1026-01635
Stantec Project Number: 185215066
Stantec File Number: TUC-26-058

Plan review for the project referenced above has been completed. This letter reflects comments to be addressed. PLEASE send all responses to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
B II-A 142 1 Yes No
Separate Permits: Automatic fire sprinklers.
Deferred Submittals: None.
Special Inspections: None.

ARCHITECTURAL COMMENTS

Sheet A1

1. It appears that a plumbing shaft has been chopped through to add a door. The two open ends of the shaft have been infilled with a “new partition” (i.e. Keyed Note 1). First, the wall infills are not hatched per the legend. Second, suspect that this shaft is a fire-rated shaft designed to meet 2024 IBC Sec. 713, and as a 6 story building the fire rating of the shaft is 2-hours. Third, how are you maintaining the shaft horizontally over the new door? Please clarify on the plans.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Joel Svoboda, RA
Senior Associate
520-545-7415