Permit Number: TC-COM-1025-01982
Parcel: 137055240

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1025-01982
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/30/2025 Commercial Mechanical Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1025-01982
ADDRESS/PARCEL: (1185 W IRVINGTON RD Unit:UNIT 155 TUCSON, AZ 85714)
The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

1. Include a site plan that shows the location of the work being done and how many units are being replaced. Reference: Section 107.2.1, IBC 2018.
2. Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation for the building to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided. Reference: Section C503.4, IECC 2018.
10/29/2025 PDSD Application Completeness Express REVIEW COMPLETED