Permit Number: TC-COM-1025-01975
Parcel: 11445262B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1025-01975
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/28/2025 Commercial Mechanical Express REQUIRES RESUBMIT Provide calculations showing the EER (i.e., BTUH/Watts at 95 F) and IEER (i.e., EER calculated at 100%, 75%, 50%, and 25% load conditions) for the submitted split system AC unit based on data from the manufacturers of the condensing unit and the evaporator coils. Reference: Section C403.3.2, IECC 2018.
10/27/2025 PDSD Application Completeness Express REVIEW COMPLETED