Permit Number: TC-COM-1025-01968
Parcel: 127022690

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1025-01968
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/24/2025 Addressing Validation REQUIRES RESUBMIT Address on permit application and gas template do not match. Permit application lists an address of 5324 E 1st St, Bldg 1, the gas template lists an address of 5324 E 1st St. If the address on the application is incorrect, please submit a Request Change of Address. If the address on the gas template form is incorrect, please correct and resubmit. How to request a change of address:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/withdraws-and-extensions.pdf
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov
10/27/2025 Commercial Plumbing Express REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1025-01968
ADDRESS/PARCEL: (5324 E 1ST ST Unit:BLDG 1 TUCSON, AZ 85711)
COMMENTS:
1. The pipe size from the meter appears to be undersized. With Schedule 40 metallic pipe and a total demand load of 305,000 BTU with a developed length of approximately 75 feet, the initial segment from the meter is required to be a minimum of 1-1/4 inch per 2018 IFGC Table 402.4(1).
10/24/2025 PDSD Application Completeness Express REVIEW COMPLETED