Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1025-01944
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/23/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/23/2025 | Commercial Plumbing Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-COM-1025-01944 ADDRESS/PARCEL: (3926 S 12TH AV Unit:UNIT 1 TUCSON, AZ 85714) COMMENTS: 1. Please specify the type of gas piping being used (e.g., black iron, polyethylene, etc.) and indicate which sizing table from the 2018 IFGC you are referencing. Based on the information shown, the pipe size from the meter appears to be undersized. a. For example: If Schedule 40 metallic pipe is being used and the total connected load is 200,000 BTU with a developed length of approximately 68 feet, the initial segment from the meter is required to be a minimum of 1-1/4 inch per 2018 IFGC Table 402.4(1). |
||