Permit Number: TC-COM-1025-01940
Parcel: 123060420

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1025-01940
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/27/2025 Commercial Electrical APPROVED
11/03/2025 Site Zoning APPROVED
11/03/2025 Water - PDSD APPROVED
10/31/2025 Site Engineering NOT REQUIRED
11/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/03/2025 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide a dimension on the drawings to indicate the new wall will provide a minimum of 5 feet clear floor space from the existing wall to the new wall. 2009 ICC A117.1 604.3.1
2. Provide grab bars per the requirements of 2009 ICC A117.1 604.5
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov


Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/03/2025 Commercial Mechanical REQUIRES RESUBMIT Show how the new restroom is to be ventilated. Ventilation for restrooms in public spaces requires a minimum of 50 CFM of mechanical exhaust per water closet or urinal if the exhaust is continuous and 70 CFM if the exhaust is intermittent. Reference: Sections 401.2 and 401.3, and footnote e, Table 403.3.1.1, IMC 2018.
11/03/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Provide specifications for the lavatory and water closet. Reference: Sections 303.4 and 402, IPC 2018.
2. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2018.
4. Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018 (e.g. 24” for a ½” pipe, 6” for a ¾” pipe).
5. The minimum size for a fixture drain for a lavatory is 1-1/4”. Reference: Section 706.2 and Table 709.1, IPC 2018.
6. Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. With the exception of water closets, the vent connection to a fixture drain shall not be located below the trap weir. Reference: Sections 901.2.1 and 909.2, IPC 2018.
11/03/2025 Fire New Construction REVIEW COMPLETED
10/20/2025 PDSD Application Completeness Express REVIEW COMPLETED