Permit Number: TC-COM-1025-01929
Parcel: 14118523A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1025-01929
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2026 Commercial Electrical Standard APPROVED Electrical (E) Reviewer
Ron Ross; rross@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/5/2026
01/16/2026 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Perry Hendershott; phendershott@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/14/2026
01/06/2026 Outdoor Lighting Standard APPROVED https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf
01/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/16/2026 Commercial Building Standard REQUIRES RESUBMIT Structural (S) Reviewer
Madeline Nelson; mnelson@safebuilt.com
Discipline Status:Denied
Date Completed: 1/16/2026
1.Acknowledged
2.[Unresolved] General / Firm Registration:Per the Arizona Revised Statutes, Chapter 32, Rule 141, a firm shall not
engage in the practice of any board-regulated profession or occupation unless the firm is registered with the board”.
The construction documents must indicate the name and registration number of the engineering firm by which the
signing engineer is employed. Please update the construction documents to comply with this provision. Refer to the
Arizona State Board of Technical Registration (https://btr.az.gov/) for more information.
i.Clarification:The statute listed above applies to any firm providing professional services, and therefore would
include the Engineer of Record (operating as a solo practitioner) and the specialty engineer designing the pre-
fabricated metal building. Per ARS Section 32-101(B)(13), a "Firm" means any individual or partnership,
corporation or other type of association... who offers to the public professional services regulated by the Board."
Please ensure that both the EOR and the specialty engineer have had their firms registered with the AZ State
Board of Technical Registration (https://btr.az.gov/firm-branch-alarm-businesses).
3.[Unresolved] General / Geotechnical Report:Please provide a copy of the site-specific geotechnical report referenced
in the structural general notes. The report should support the appropriateness of the selected foundation system for
the project site. All submitted geotechnical reports must be dated no later than three years from the submittal date.
Outdated reports must be accompanied by a letter from a qualified geotechnical engineer stating that the report
requirements are still valid, or stating what items may have changed. All building code references must be updated to
the current code adopted by the City.
i.Clarification:At this time, no geotechnical report has been uploaded to the portal for review.
4.Resolved
5.Acknowledged
6.[Unresolved] General / Design Assumptions:The following structural design information shall be included in the
construction documents per 2018 IBC Section 1603. Please include the following items in the structural general
notes.
i.Risk category
ii.Roof live load
iii.Wind design data
a.Wind speed, Vult

b.Exposure category
c.Internal pressure coefficient
d.Design wind pressures for exterior component and cladding materials, expressed in psf
iv.Seismic design data
a.Seismic importance factor, Ie
b.Mapped spectral response acceleration parameters, Ss and S1
c.Site class
d.Design spectral response acceleration parameters, SDS and SD1
e.Seismic design category
f.Basic seismic-force resisting system(s)
g.Design base shear(s)
h.Seismic response coefficient(s), Cs
i.Response modification coefficient(s), R
j.Analysis procedure used
v.Geotechnical Information: Design load bearing value of soils
vi.Clarification:At this time, structural drawings of the pre-fabricated metal building have not been uploaded to the
portal for review. The items above could not be located in the foundation drawings or the calculation package
provided by EOR Patrick Barrick. Therefore, this comment remains outstanding. [Please note, it is acceptable
to submit drawings for the PFMB at a later date as a deferred submittal, but the above design criteria is
required prior to permit issuance.]



Building (B) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 1/8/2026
01/16/2026 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Denied
Date Completed: 1/12/2026

1.(UNRESOLVED) - General -Provide COMcheck Mechanical Compliance Certificate. Any other APPROVED certifying
agency is acceptable. - 2021 IECC Section C403.3.2 HVAC equipment performance requirements
◦Mechanical Compliance Certificate not provided.


4.(UNRESOLVED) - Plan Sheet A1.0 -Shows a Paint Booth. Provide signed and sealed paint booth plans. If applicable
provide listed manufacture paint booth plans. - 2015 IECC Section C103.2Information on construction documents. -
2018 IBC Section [A]107.2.1Information on construction documents.
◦Add the Spray Booth to O/A ventilation schedule. Makeup air for the spray booth is not noted/identified
anywhere on the plans. Add the Spray booth exhaust fan specifications to the Exhaust fan schedule.
Show/identify the required O/A makeup for the Spray Booth. Provide Manufacturer Listed Paint booth submittal
to inspector at time of Mechanical inspections. Provide Fire sprinkler plan for spray booth to Fire Dept. for Fire
Review.
01/28/2026 Site Engineering Standard REQUIRES RESUBMIT Site Engineering Review

TC-COM-1025-01929
9368 E OLD VAIL RD

Summary: GRACE PACIFICA MACHINING - WORKSHOP AND OFFICE PHASE 1

Site Engineering comments are as follows:

1. This commercial building permit cannot be approved until the associated development package, TD-DEV-0325-00065, is approved by all reviewers. UDC Article 3.3.3.7.a.
2. Please re-submit this permit once the revision to the above-mentioned Development Package is approved.

To re-submit, visit the Tucson Development Center Online at:
https://tdc-online.tucsonaz.gov/#/home

The instructions for resubmittal can be found at: Revisions and Resubmittals

Engineering Associate: Ryan Insalaco
ryan.insalaco@tucsonaz.gov
01/28/2026 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1025-01929 – TD-DEV-0325-00065
9368 E. Old Vail Rd. Tucson, AZ 85747
New industrial manufacturing building w/ parking, landscape, and drainage improvements (2nd Review)

TRANSMITTAL DATE: 1/28/2026

This site is located in the I-2 zone (UDC 4.7.30).

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: Zoning has conducted a cursory review of the building permit plan set and while it appears the site plan is now consistent with the associated Development Package (DP), Site Zoning cannot approve this building permit until the revision to TD-DEV-0325-00065 has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
01/27/2026 Fire New Construction Standard REVIEW COMPLETED
01/05/2026 PDSD Application Completeness Express REVIEW COMPLETED