Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-COM-1025-01918
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/28/2025 Commercial Plumbing Express REQUIRES RESUBMIT The proposed atmospheric gas water heater is not allowed to be located in a closet that opens to a bathroom. A direct vent water heater has a sealed combustion system (i.e., it takes all its combustion air from outside and no products of combustion are released into the interior of the building). [Initial comment: The gas-fired water heater being replaced is said to be located in a closet that opens to a bathroom. This requires the water heater (and any other gas-fired appliance in the same location) to be a direct vent appliance. Provide the specifications for the proposed replacement water heater. Reference: exception 1, Section 303.3, IFGC 2018.]
10/28/2025 PDSD Application Completeness Express REVIEW COMPLETED