| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/20/2025 | Commercial Plumbing Express | REQUIRES RESUBMIT | The gas-fired water heater being replaced is said to be located in a closet that opens to a bathroom. This requires the water heater (and any other gas-fired appliance in the same location) to be a direct vent appliance. Provide the specifications for the proposed replacement water heater. Reference: exception 1, Section 303.3, IFGC 2018. | ||