Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1025-01906
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/31/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/15/2025 | Addressing Validation | REQUIRES RESUBMIT | Site plan missing complete project address. Update site plan and resubmit. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@Tucsonaz.gov | ||
| 10/30/2025 | Commercial Building | REQUIRES RESUBMIT | Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed. 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete architectural plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf Additionally, be sure to have the registrant include the following. Complete Code analysis for the proposed use of the building • Building Codes • Fire Sprinklers Yes or No • Design Occupant Load • Total square footage of Occupied Space. Complete site plan Complete dimensioned floor plan Complete egress plan Compliance with the Accessibility requirements in IEBC 205.7 Please contact me if you have any questions about these comments. Mark Masek Plans Examiner – Building Safety Planning and Development Services | City of Tucson main 520.837.4994 email mark.masek@tucsonaz.gov |
||
| 10/22/2025 | Commercial Electrical | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1025-01906 (3225 N SWAN RD Unit:UNIT 117 TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). Electrical Review: 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf 2. Provide an electrical plan showing any/all electrical work specific to the the scope of work being done at the buildings and site. Plans shall include (as necessary for scope of work), but may not be limited to items below: 3. Provide electrical load calculations, for the Main Panels, Per NEC 220.40. 4. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4. 5. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1. 6. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number. 7. Show all GFCI protection (NEC 210.8(B)) in readily accessible location per NEC 210.8. receptacles behind appliances or in cabinets may require labeled GFCI protection in a readily accessible location or with GFCI breakers. Additional comments may be forthcoming with complete electrical plans for the building and site. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/29/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Provide a mechanical design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018. | ||
| 10/29/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Provide a plumbing design and calculations performed by an Arizona registrant who has demonstrated proficiency through registration, education, technical knowledge, or experience to perform such work. Reference: Sections 107.1 and 107.2.1, IBC 2018. | ||
| 10/30/2025 | Fire New Construction | REQUIRES RESUBMIT | 1. Resolve all other comments. 2. Provide a full set of plans. john.vincent@tucsonaz.gov 5203495581 |
||
| 10/31/2025 | Site Zoning | REQUIRES RESUBMIT | PDSD TRANSMITTAL FROM: Bobby Parsons PDSD Zoning Review Section PROJECT: TC-COM-1025-01906 3225 N Swan Rd. Unit 119 Tucson, AZ 85712 Framing 4 walls to create office and break rooms (1st Review) TRANSMITTAL DATE: 10/31/2025 Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed. This site is located in the C-1 zone (UDC 4.7.20). 1. Comment: Clearly define the proposed use of the Unit as outlined in the Unified Development Code (UDC Table 4.8-4) and if applicable, include any Use Specific Standards associated with the use. 2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted. If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov. |
||
| 10/15/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |