Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2025 Site Zoning Standard APPROVED
11/06/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/06/2025 Commercial Building Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1025-01897
ADDRESS/PARCEL: (5870 E 14TH ST Unit: BLDG 3 TUCSON, AZ 85711)

COMMENTS:
1. Please indicate whether this permit application requires a Certificate of Occupancy be issued.
2. Code Review/Analysis
a. Please correct the year of the code used as IBC 2018.
b. Please add ICC A117.1 - 2017 Accessible & Usable Building & Facilities
c. Enumerate/list the occupant loads from the various spaces. Provide a total at the bottom.
d. List the Fire Alarm requirement.
e. List the Fire Sprinkler requirement and the response from Tucson Fire Department.
f. Minimum required plumbing fixtures. (NOTE: Should the following facilities be available in other location, please locate them on the site plan and provide their distance to this building.)
i. Water Closet
1. Provide the calculation for MEN based on the occupant load.
2. Provide the calculation for WOMEN based on the occupant load.
ii. Lavatory
1. Provide the calculation for MEN based on the occupant load.
2. Provide the calculation for WOMEN based on the occupant load.
iii. Service/Mop sink, please locate/label on the plan.
iv. Drinking Fountain, please locate/label on the plan.
3. Panic Hardware: Assembly space
a. Swinging doors serving a Group H occupancy & swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware.
b. The doors shall swing in the direction of egress travel. IBC 1010.1.10
4. Egress Plan
a. Please provide and egress plan providing the following.
i. Egress route path.
ii. Length of travel from the farthest point to the point of exit.
iii. At point of exit.
1. Provide the calculated exit width.
2. Provide the provided exit width.
3. Provide the number of occupants exiting.
b. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. IBC 1016.2
5. Basement
a. Indicate the height clearance.
b. Locate the water heater.
i. Indicate that it is fueled by gas.
c. Locate the Electrical Panel.
d. Label as storage.
i. List hazardous material being stored and the quantity.
e. Indicate the Occupancy Use.
i. Is it S-1
ii. Is it S-2
6. Door at the top of the stair from the basement.
a. Current floor plan shows a door opening into a classroom space.
b. The above condition is not ideal. The basement should empty directly to the exterior that is open to the sky.
7. Other items mentioned in the phone conversation.
a. Stage
i. Door replacing window, leading to a landing and ramp. Reflect these on the floor plan drawings.
ii. Provide landing and ramp drawings.
b. Assembly
i. Door replacing window, leading to a landing and ramp. Reflect these on the floor plan drawings.
ii. Provide landing and ramp drawings.
c. Office #1
i. You have a note: 1 exit required, need ramp & stairs.
ii. Please correct your floor plan reflecting the above.
iii. Please provide ramp and stair drawings.
8. Ensure to comply to ICC A117.1 for accessibility including compliant door clear openings.
9. Please resubmit.

Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
10/29/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1025-01897 (5870 E 14TH ST Unit:BLDG 3 TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Electrical Review:
1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans, design, and calculations, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304, 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/checklists/commercial_submittal_requirements_july2023.pdf
2. Provide an electrical plan showing any/all electrical work specific to the the scope of work being done at the buildings and site.
3. Show electrical outlets, panels and other penetrations within fire-rated walls, floors and ceilings with fire ratings. IBC 714.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/04/2025 Commercial Mechanical Standard REVIEW COMPLETED
11/05/2025 Fire New Construction Standard REVIEW COMPLETED
10/14/2025 PDSD Application Completeness Express REVIEW COMPLETED