Permit Number: TC-COM-1025-01887
Parcel: 138110170

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-1025-01887
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2025 Commercial Electrical Express PENDING ASSIGNMENT
10/16/2025 PDSD Application Completeness Express REQUIRES RESUBMIT Incomplete Submittal: 1. The electrical diagram submitted has the incorrect address, please update and resubmit. 2. Show overcurrent protection not exceeding the allowable conductor ampacity, NEC 230.90(A). The ampacity rating of the 2/0 Cu conductors is 175A. The main breaker cannot exceed this value. Please upsize the conductors, or downsize the Main Breaker.
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov