Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.4
Permit Number - TC-COM-1025-01886
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.4
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2025 | Addressing Validation | REQUIRES RESUBMIT | Site plan missing project address (listed address is incorrect). Please update address on site plan and resubmit. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov | ||
| 10/17/2025 | Commercial Electrical Express | REQUIRES RESUBMIT | >>> This comment was not addressed on the plans submitted. 1. Show overcurrent protection not exceeding the allowable conductor ampacity, NEC 230.90(A). The ampacity rating of the 2/0 Cu conductors is 175A. The main breaker cannot exceed this value. Please upsize the conductors, or downsize the Main Breaker. |
||
| 10/16/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |