Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1025-01886
Parcel: 138110170

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - TC-COM-1025-01886
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2025 Addressing Validation PENDING ASSIGNMENT
10/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2025 Commercial Electrical Express PENDING ASSIGNMENT
10/16/2025 PDSD Application Completeness Express REQUIRES RESUBMIT Incomplete Submittal: 1. The site plan submitted has an incorrect address, please update and resubmit. 2. The electrical diagram submitted has the incorrect address, please update and resubmit. 3. Show overcurrent protection not exceeding the allowable conductor ampacity, NEC 230.90(A). The ampacity rating of the 2/0 Cu conductors is 175A. The main breaker cannot exceed this value. Please upsize the conductors, or downsize the Main Breaker.
Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov