| 10/16/2025 | Addressing Validation | PENDING ASSIGNMENT | |||
| 10/16/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2025 | Commercial Electrical Express | PENDING ASSIGNMENT | |||
| 10/16/2025 | PDSD Application Completeness Express | REQUIRES RESUBMIT | Incomplete Submittal: 1. The site plan submitted has an incorrect address, please update and resubmit. 2. The electrical diagram submitted has the incorrect address, please update and resubmit. 3. Show overcurrent protection not exceeding the allowable conductor ampacity, NEC 230.90(A). The ampacity rating of the 2/0 Cu conductors is 175A. The main breaker cannot exceed this value. Please upsize the conductors, or downsize the Main Breaker. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf For questions: maribel.arevalo@tucsonaz.gov |