Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/16/2025 Commercial Electrical Express REQUIRES RESUBMIT The provided riser diagram has the incorrect address on it. Please provide the sheet with the correct address or TEP will not provide clearance.

>>> The following needs to be fixed on the plans:
Show overcurrent protection not exceeding the allowable conductor ampacity, NEC 230.90(A). The ampacity rating of the 2/0 Cu conductors is 175A. The main breaker cannot exceed this value. Please upsize the conductors, or downsize the Main Breaker.
10/16/2025 PDSD Application Completeness Express REVIEW COMPLETED