Permit Number - TC-COM-1025-01885
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2025 | Commercial Electrical Express | REQUIRES RESUBMIT | The provided riser diagram has the incorrect address on it. Please provide the sheet with the correct address or TEP will not provide clearance. >>> The following needs to be fixed on the plans: Show overcurrent protection not exceeding the allowable conductor ampacity, NEC 230.90(A). The ampacity rating of the 2/0 Cu conductors is 175A. The main breaker cannot exceed this value. Please upsize the conductors, or downsize the Main Breaker. |
||
| 10/16/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |