Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-COM-1025-01884
Parcel: 10706035A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1025-01884
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2026 Commercial Building Standard APPROVED
04/27/2026 Commercial Electrical Standard APPROVED
04/14/2026 Site Engineering Standard APPROVED
04/27/2026 Site Zoning Standard APPROVED
04/30/2026 Water - PDSD Standard APPROVED
04/30/2026 Commercial Plumbing Standard NOT REQUIRED
04/27/2026 Outdoor Lighting Standard NOT REQUIRED No changes from the previously approved outdoor lighting.
05/04/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/30/2026 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide the specifications for the new HVAC units (e.g. manufacturer, model number, heating/cooling capacity, and efficiency ratings). All single-phase heat pumps not operational on January 1, 2023, in the Southwest region, must have an EnergyGuide label identifying a minimum 14.3 SEER2 rating and a 7.5 HSPF2 rating. Reference: Section 301.7, IMC 2018.
2. Show how the outside air will be supplied to the ventilated areas. Reference: Sections 401.2 and 401.3, IMC 2018.
If you have any questions about this review comment, I can be reached at Robert.Sherry@tucsonaz.gov
05/01/2026 Fire New Construction Standard REVIEW COMPLETED
04/10/2026 PDSD Application Completeness Express REVIEW COMPLETED