Permit Number: TC-COM-1025-01884
Parcel: 10706035A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1025-01884
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2025 Commercial Building Standard APPROVED Rhonda, I called your office regarding combining building phase II and phase III into one certificate of occupancy. It looks like phase II does not have the proper certificate of occupancy. It will be done like so - STORAGE (2065 sf Phase II, 2383 sf Phase III)
10/27/2025 Commercial Electrical Standard APPROVED
10/27/2025 Outdoor Lighting Standard APPROVED
11/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/04/2025 Commercial Mechanical Standard REQUIRES RESUBMIT 1. Provide specifications for the proposed split-system heat pump. Clarify the proposed capacity of the system; a 3-ton system has a nominal airflow rate of 1200 CFM, not 2000 CFM. Reference: Section 301.7, IMC 2018.
2. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C403.3.1, IECC 2018.
3. Show the size, routing, and termination of the condensate drain for the heat pump. Reference: Section 307.2.1, IMC 2018 as amended by the City of Tucson.
4. Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted during the hours of occupancy (i.e., the exhaust fans shall operate even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.
5. Secure the refrigerant circuit access ports of the outside unit of the heat pump to prevent unauthorized access. Reference: Section 1101.10, IMC 2018.
11/04/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Re-plot drawing P-2.0 to include the fixture unit calculations and the plumbing schedule that were cut out of the viewport. Reference: Section 107.2.1, IBC 2018.
2. Clarify the description of the lavatory faucet. The description refers to “touchless faucets” but the model number of the faucet has two lever handles. Provide metering faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Specify that the tempered water for the lavatories is to be provided by using approved devices conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
4. Provide cleanouts that are the same size as the pipe that they serve. Reference: Section 708.1.5, IPC 2018.
5. Provide sizing calculations and dimensions of the gutters and downspouts. Verify the area being drained by the proposed gutter (i.e., does the roof of the existing building drain onto the new roof). Reference: Sections 1106.1 and 1106.6, IPC 2018.
11/03/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1025-01884
Location: 1315 W MIRACLE MILE
Review Date: 11/3/2025
Site Engineering Comments:
1. For the approved development package TD-DEV-0424-00126, It is called out that building # 4 is to be office (678 SF) and Storage (1652 SF) for a total of 2,330 SF. The proposed commercial plans show 2515 SF. It is required that the commercial plans match the approved development package plans. If changes are proposed, then a revision to the development package will be required.
2. Is the only roof downspout going to be located at the Northeast corner of existing building #3? If not provide call outs for all building downspouts. If they do not match what is provided for TD-DEV-0424-00126 then a revision to the development package will be required.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
11/05/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-COM-1025-01884
1315 W. Miracle Mile Tucson, AZ 85705
Addition to existing building (1st Review)

TRANSMITTAL DATE: 11/5/2025

This site is located in the C-2 zone (UDC 4.7.21). Vehicle Rental and Sales is an allowed use subject to Use Specific Standard 4.9.9.G.1 & .2.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The associated Development Package (DP) TD-DEV-0424-00126 lists the square footage of building #4 as 2,330 sq. ft. (678 sq. ft. office & 1,652 sq. ft. storage) however the plans submitted for this permit list building #4 as 2,515 sq. ft. and being used for storage. The building plans, including square footage and height, need to match what was approved in the DP. If changes are proposed, a revision to the DP will be required.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
11/04/2025 Water - PDSD Standard REQUIRES RESUBMIT Show the location, size, and serial number of the existing water meter. Show the location and size of the backflow preventer, and the water service pipe on a site plan. Reference: Section 107.2.1 and 107.2.6, IBC 2018.
11/04/2025 Fire New Construction Standard REVIEW COMPLETED
10/14/2025 PDSD Application Completeness Express REVIEW COMPLETED