Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1025-01827
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2025 | Site Engineering Standard | APPROVED | |||
| 10/30/2025 | Site Zoning Standard | APPROVED | Associated DP (TD-DEV-0425-00123) has been issued. | ||
| 10/30/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/30/2025 | Commercial Building Standard | REQUIRES RESUBMIT | Resolve Fire Code comments | ||
| 10/23/2025 | Commercial Electrical Standard | REQUIRES RESUBMIT | Commercial Elecctrical Review TC-COM-1025-01788, TC-COM-1025-01826, TC-COM-1025-01827, TC-COM-1025-01828, TC-COM-1025-01829, TC-COM-1025-01830 (1202 W MIRACLE MILE TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. Show PV interconnection, at TEP Meter #169206744, in compliance with NEC 705.32. Reference also NEC 230.95. 705.32 Ground-Fault Protection. 2. Provide rapid shutdown labels and placard on the building for Array #2 at the location of INV 8 & 9. NEC 690.56(C) & 705.10. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/27/2025 | Fire New Construction Standard | REQUIRES RESUBMIT | -Provide 4' perimeter pathways on the clubhouse building per IFC 2024, 1205.3.1 john.vincent@tucsonaz.gov 5203495581 |
||
| 10/22/2025 | Outdoor Lighting Standard | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-1025-01788, TC-COM-1025-01826, TC-COM-1025-01827, TC-COM-1025-01828, TC-COM-1025-01829, TC-COM-1025-01830 (1202 W MIRACLE MILE TUCSON, AZ 85705) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). Outdoor Lighting Review: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf 1. Please clarify if there are any outdoor lighting fixtures being added under the solar canopies. If new lighting fixtures are being added or modifications are being made to the existing outdoor lighting, then please show compliance with the OLC as detailed in comments 2-9. 2. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan. 3. List the Lighting Area per OLC (Typically E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation. 5. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. 6. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf 8. Specify any exceptions used. 9. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/08/2025 | PDSD Application Completeness Express | REVIEW COMPLETED | SHARED STUDIO SESSION ON 580-117-567; MASTER SET OF CONSTRUCTION PLANS ARE LOCATED ON PERMIT: TC-COM-1025-01788/ROOF ARRAY 2, New solar PV system to supplement resident usage throughout the community. The system will consist of 418 solar panel mounted on elevated solar racking's over the existing parking's spaces ("solar carports") and on rooftops in common areas. with reviews to be conducted for: TC-COM-1025-01826/CARPORT ARRAY 1, TC-COM-1025-01827/CARPORT ARRAY 3, TC-COM-1025-01828/CARPORT ARRAY 4, TC-COM-1025-01829/CARPORT ARRAY 5, TC-COM-1025-01830 CARPORT ARRAY 6 |