Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-COM-1025-01819
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/08/2025 | Commercial Electrical Express | REQUIRES RESUBMIT | Commercial Electrical Review TC-COM-1025-01819 (5861 E NORTH ST TUCSON, AZ 85712) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC). 1. There are 3 separate meter/panels being replaced. This will require separate permits for each address. Please file for 2 more permits for the other two addresses that the meters are associated with. 2. Provide an electrical riser diagram, 2017 NEC 230.9. Notate the grounding and bonding method, 2017 NEC 250.20(B), 250.24, 250.30(A)(4). Metallic gas lines must be bonded and not be used as the primary grounding method, 2017 NEC 250.50, 250.52(B)(1). 3. Show the location of the panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A) Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 10/07/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |