Permit Number: TC-COM-1025-01805
Parcel: 11716008A

Address:
191 E TOOLE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1025-01805
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2025 Commercial Electrical Standard APPROVED
10/27/2025 Site Zoning Standard APPROVED
10/27/2025 Water - PDSD Standard APPROVED
10/17/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
10/08/2025 Site Engineering Standard NOT REQUIRED
10/27/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/27/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please amend the plans to show compliance with IEBC 305.7. This code section requires that accessibility be provided to the altered spaces. Where the existing path of travel elements, which entails a primary entrance, a primary path of travel, sanitary facilities serving the area, a drinking fountain, and signs.
A. For example, it doesn’t appear the stage is accessible, provide amend the plans to provide accessible access to the stage. IBC 1103.1
1. If the cost of providing or upgrading the items above to be accessible is disproportionate to the cost of construction (exceeds 20% of the cost of construction not including accessibility upgrades), please provide information to verify construction costs. If this exemption is taken, accessibility upgrades equaling 20% of the cost of the project shall be made.


Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/27/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Provide information on the sequence of operation for the restroom exhaust fan (i.e., how is the fan controlled?). Reference: Section 403.2.1 (4), IMC 2018.
10/27/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Show the return piping for the recirculated hot water for the water heater on the plans and detail. Reference: Section 107.2.1, IBC 2018.
2. Provide third-party listing and material standards for all plumbing fixtures. Reference: Sections 303.4 and 402, IPC 2018
3. Provide shower valves that comply with the requirements of Section 412.3, IPC 2018.
4. Provide tempered water for the restroom lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018.
5. Provide a metering faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10 seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
6. If the shower does not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018.
7. Revise the design of the hot water supply to the restroom lavatory so that the distance from the hot water source to the hot water termination for the public lavatory complies with the requirements of Section C404.5, IECC 2018 (i.e. 24” maximum distance for ½” pipe).
10/27/2025 Fire New Construction Standard REQUIRES RESUBMIT Resolve all building comments.

john.vincent@tucsonaz.gov
5203495581
10/06/2025 PDSD Application Completeness Express REVIEW COMPLETED