Permit Number: TC-COM-1025-01789
Parcel: 12513002F

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1025-01789
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/24/2025 Commercial Building Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide a project specific statement of special inspections for this project, stating requirements for the special inspections and required tests. IBC 107.2.1, IBC 1704, IBC 1705

Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf
2. Provide the signed and sealed structural calculations, prepared by an Arizona licensed registrant, used in the design of this project. IBC 107.2.7




Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
10/15/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1025-01789 (3232 E SPEEDWAY BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Reference sheet E400, ‘Circuit ID’ XFMR-1 to UTILITY DG METER and UTILITY DG METER to ACDS-1, OCPD sizes. This sheet shows an OCPD of 350A for these circuits. But the line diagrams on Sheets E200 and E300 show a fused disconnect of 400A. These two OCPD sizes should match at 350A. Please clarify and fix this discrepancy.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/15/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1025-01789 (3232 E SPEEDWAY BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Show lamps with a maximum of 3500K color temperature, OLC 402.1. Provided light fixtures are listed at 4000K color temperature.
2. Note on the Sheet L100 that the light fixtures are all full-cutoff, 401.2.1(3).


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
10/30/2025 Site Engineering Standard REQUIRES RESUBMIT TC-COM-1025-01789
3232 E SPEEDWAY BL

Site Engineering Comments are as follows:
1. This proposed commercial building permit will require a Development Package that complies with the criteria found in Administrative Manual 2-06.4.0 thru 2-06.4.9.
https://codelibrary.amlegal.com/codes/tucson/latest/tucson_az_udc/0-0-0-8794
2. This project lies withing the boundaries of the Christmas Wash floodplain. The development package and this building permit may share a single Floodplain Use Permit. Once the application for the Development Package is submitted, navigate to the sub-records tab and apply for Floodplain use permit.

Ryan Insalaco
Engineering Associate
ryan.insalaco@tucsonaz.gov
10/28/2025 Site Zoning Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
PDSD Zoning Review Section

PROJECT:
TC-COM-1025-01789
3232 E. Speedway Blvd. Tucson, AZ 85716
Installation of carports in the parking lot (1st Review)

TRANSMITTAL DATE: 10/28/2025

Comment: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 (UDC 4.7.21) and R-3 (UDC 4.7.12) zones.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming based on responses to zoning comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
10/20/2025 Fire New Construction Standard REVIEW COMPLETED
10/02/2025 PDSD Application Completeness Express REVIEW COMPLETED