Permit Number: TC-COM-1025-01788
Parcel: 10706014G

Review Status: In Review

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1025-01788
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
08/03/2026 Site Engineering Standard NOT REQUIRED
08/18/2026 Site Zoning Standard NOT REQUIRED
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Building Standard PENDING ASSIGNMENT
N/A Fire New Construction Standard PENDING ASSIGNMENT
08/17/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1025-01788 (1202 W MIRACLE MILE TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show PV interconnection, at TEP Meter #169206744, in compliance with NEC 705.32. Reference also NEC 230.95. 705.32 Ground-Fault Protection.
2. Clarify the wire count in wire TAG #6, Sheet E201. Each conduit should contain the parallel ungrounded conductors and the grounded conductor(neutral) and grounding equipment conductor(GEC). NEC 310.10, 310.10(G). Must have the same number of conductors in each parallel conduit.
07/31/2026 PDSD Application Completeness Express REVIEW COMPLETED