Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1024-02087
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/26/2024 | Site Zoning | APPROVED | |||
| 11/26/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/11/2024 | Commercial Building | REQUIRES RESUBMIT | 1. Sheet a1.0 Show occupancy type of adjoining business | ||
| 11/11/2024 | Commercial Electrical | REQUIRES RESUBMIT | 1. Sheet E1.0 Provide a panel schedule for existing panel. Provide documentation showing the electrical system complies with IECC. | ||
| 11/11/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Sheet M1.0 Provide documentation Mechanical System meets IECC requirements. | ||
| 11/11/2024 | Commercial Plumbing | REQUIRES RESUBMIT | For any questions, please contact Ed Kulik: EKulik@willdan.com 1. Sheet T1.0 Provide accessible restroom per ANSI 117.1 2. Sheet P1.0 Provide a detail showing the water heater support and expansion tank. IPC 2903.4.1 |
||
| 11/14/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 10/31/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 11/15/2024 | Site Engineering | REVIEW COMPLETED |