Permit Number: TC-COM-1024-02085
Parcel: 13419042D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-02085
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2024 Water - PDSD APPROVED
11/26/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/14/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 11/14/2024 6:09:15 PM
1. GENERAL - UPDATES: For project updates, please submit sheets with all changes clearly marked in revision clouds.
Please provide a written response to each comment; updates without a clear response to all comments may not be reviewed. If you have any questions regarding the comments, you may contact me directly. Updates may result in
additional comments.
2. GENERAL - MECHANICAL LOADS: The Mechanical Plan, M1.0, and the Mechanical Schedules, M2.0, indicate that new rooftop equipment is being installed. Because these units exceed 300 lb, a professional engineer is required to
evaluate the existing framing and provide documentation that the roof has sufficient capacity to support the proposed loads. This documentation must carry the seal and signature of the evaluating engineer. If reinforcement of the roof is
required, sealed details must also be provided.







Building(B) Reviewer
Andrew Bevis
abevis@safebuilt.com
Approved
Reason:
Date Completed : 11/11/2024 11:37:44 AM





Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/14/2024 5:58:09 PM






Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 11/4/2024 6:25:38 PM
1. E2.1 Missing description for Power Plan Key Note #20.
2. E4.0 Existing Riser Diagram #1 shows a 45 amp CB feeding the 112.5 KVA transformer. This is undersized and does not correlate with MDP panel schedule on sheet E4.1. Correct/coordinate to show actual conditions. Panel names
also not coordinated.
3. E4.0 does not show new surge protection that is shown by MDP panel schedule on sheet E4.1.
4. E5.0 Should show (existing?) pull stations at all required exits. This is required per NFPA 72 and may be required per local code. Confirm if not required per local code or comply and show existing or new.






Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 11/10/2024 4:33:34 PM
First Plumbing Review:
1). General: Plan set missing plan pages P1.0 & P1.1 as stated on plan page A0.0 sheet index. Provide plan pages P1.0 &
P1.1 as stated on plan page A0.0 sheet index so a complete Plumbing & Gas review can done -2018 IPC 106.3.1
2) Plan Page P2.0: Missing fixture & appliance schedule that that listed manufacturer names & model numbers of the replaced fixtures & water heater. Add fixture & appliance schedule that that listed manufacturer names & model numbers of
the replaced fixtures & water heater. -2018 IPC 303, 402, 501.5
11/15/2024 Fire New Construction REQUIRES RESUBMIT -The exit that leads from sales to the stockroom is not approved. This does not comply with IFC 1016.2 #5 (exception 2). Either comply with this section or remove exit sign. This is a nonrequired exit since you already have two other code compliant exits.
john.vincent@tucsonaz.gov
5203495581
11/26/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1024-02085
7160 E BROADWAY BL. – C-2
General Merchandise Sales (1st Review)

TRANSMITTAL: November 26, 2024

Resubmittal requires a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the C-2 zone (UDC 4.7.21). General Merchandise Sales is an allowed use in the zone (UDC Table 4.8-4), subject to a Use Specific Standard 4.9.9.B.1

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. The exterior changes, new compactor required a DP.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/31/2024 PDSD Application Completeness Express REVIEW COMPLETED
11/15/2024 Site Engineering REVIEW COMPLETED