Permit Number: TC-COM-1024-02085
Parcel: 13419042D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1024-02085
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2025 Commercial Building Standard APPROVED Building (B) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 12/1/2025


Structural (S) Reviewer
Madeline Nelson; mnelson@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 12/2/2025
12/05/2025 Commercial Mechanical Standard APPROVED Mechanical (M) Reviewer
Jorge Valido; jvalido@safebuilt.com
Discipline Status:Approved with Comments
Date Completed: 12/1/2025
No Mechanical work in scope of job.
12/05/2025 Commercial Plumbing Standard APPROVED Plumbing (P) Reviewer
Andrew Bevis; abevis@safebuilt.com
Discipline Status:Approved As Is
Date Completed: 12/5/2025
11/26/2025 Site Engineering Standard APPROVED
12/17/2025 Water - PDSD Standard APPROVED
12/08/2025 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/18/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/05/2025 Commercial Electrical Standard REQUIRES RESUBMIT Electrical (E) Reviewer
Ron Ross; rross@safebuilt.com
Discipline Status:Denied
Date Completed: 12/1/2025
No electrical drawings were provided.
Electrical Drawings need to show location of electrical panel, panel schedule with added load and assurance/estimate of
existing and new load. Need to call out over current protection (CB size and Fuse size if used). Need to call out size and type
of disconnect. Need to call out conductors, ground size, and raceway information. Should provide a service receptacle in the
area that meets NEC 210.63.
Electrical Drawings need to be signed and sealed by a licensed design professional.
12/18/2025 Fire New Construction Standard REVIEW COMPLETED
11/26/2025 PDSD Application Completeness Express REVIEW COMPLETED
12/15/2025 Site Zoning Standard REVIEW COMPLETED