Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1024-02080
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2024 Commercial Building APPROVED
11/13/2024 Commercial Electrical APPROVED
11/22/2024 Site Zoning APPROVED
11/14/2024 Commercial Plumbing NOT REQUIRED
11/22/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/14/2024 Commercial Mechanical REQUIRES RESUBMIT Revise the ventilation calculations to show the population of the barber shop as 25 people/1,000 square feet. If the existing HVAC unit is also supplying the reception room, include it in your calculations (Office: Main Entry Lobby, 10 People/1,000 Square feet, 5.0 CFM/person, 0.6 CFM/square foot).
11/14/2024 Fire New Construction REVIEW COMPLETED
10/30/2024 PDSD Application Completeness REVIEW COMPLETED
11/15/2024 Site Engineering REVIEW COMPLETED