Permit Number: TC-COM-1024-02072
Parcel: 11706319B

Address:
300 S TOOLE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1024-02072
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/11/2024 Commercial Mechanical APPROVED
11/25/2024 Water - PDSD APPROVED
11/25/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/11/2024 Commercial Electrical REQUIRES RESUBMIT 1. Sheet FS3.0 Provide documentation that the electrical comply with IECC.
11/11/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet p1.1 Inspector to verify existing conditions in restrooms comply with ANSI 117.1
2. Sheet Pf.2 Provide details for slab repairs at plumbing trenches
11/11/2024 Commercial Structural REQUIRES RESUBMIT For questions please contact Ed Kulik ekulik@willdan.com

1. Sheet A01. Provide documentation that shows mechanical system complies with IECC.
2. Sheet a0.1 Provide a mechanical plan even if it is existing. Plan review needs to see that it complies with the new occupancy
3.Sheet a1.0 Provide occupancy type for existing building to determine separation wall requirements.
4. Sheet a3.0 Provide a floor plan showing all dimensions including ceiling heights.
5. Sheet a3.0 Show heights of all walls and partitions. Per IBC
6. Sheet a3.2 Provide ADA seating. ANSI 117.1
7. Sheet a8.0 Provide ADA access counter at lobby desk. ANSI 117.1
8. Sheet a8.1 Show accessible counter at all bar areas. ANSI 117.1
9. Sheet 9.0 Provide signage over front entry door per IBC Chapter 10. (This door shall be open while building is occupied.
10. Sheet FS5.1 List Occupancy Type for coffee house.
11. Sheet FS6.0 Show Accessible Counter at each POS locations.
11/15/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1024-02072
300 S TOOLE AV

Site engineering comments are as follows:
1. Please resolve Historic conditions. See Zoning comment.
Ryan Insalaco
Email: ryan.insalaco@tucsonaz.gov
Phone: (520) 837-5351
11/15/2024 Site Zoning REQUIRES RESUBMIT FROM: Ramiro Olivarez
PDSD Zoning Review Section

PROJECT: TC-COM-1024-02072
Commercial Alteration (1st Review)
300 S TOOLE AV TUCSON, AZ 85701 – I-1 Zone

TRANSMITTAL DATE: 11/15/2024


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: Zoning has reviewed the plan and while it is completed the Historic review process needs to be approved and completed before Zoning can approve it.

02. COMMENT: Additional comments may be forthcoming on the next review based on the proposed use and applicable use specific standards.


If you have any questions about this transmittal, Contact by email Ramiro.Olivarez@tucsonaz.gov
11/13/2024 Fire New Construction REVIEW COMPLETED
11/15/2024 Historic REVIEW COMPLETED The Special District minor review application submittal is complete. This project is outside local HPZ (Armory) boundary. It is not in any National Historic District. A review of the plans and discussing with zoning review staff, it appears only interior modifications are being proposed. Based on these facts HPZ review is NOT required for this project. It is in the archeological sensitivity zone. Contact the historic office if any digging will be involved.
If you have any historic questions, contact Michael.Taku@tucsonaz.gov
10/30/2024 PDSD Application Completeness REVIEW COMPLETED