Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1024-02071
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2024 | Fire New Construction | NOT REQUIRED | |||
11/14/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/12/2024 | Commercial Building | REQUIRES RESUBMIT | N/A | ||
11/13/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Provide an electrical symbols legend for all electrical and lighting symbols associated with this project. 2 Provide compliance with the 2012 City of Tucson Outdoor Lighting Code for the exterior lighting. REF; 2018 IBC section 107.2.1, 2012 City of Tucson Outdoor Lighting Code, 2017 NEC. |
||
11/14/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide calculations to verify that adequate ventilation will be provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018. 2. Show the location of the outside unit. If the outside unit is not located in a secure location, secure the refrigerant circuit access ports of the outside unit to prevent unauthorized access. Reference: Section 1101.10, IMC 2018. |
||
10/30/2024 | PDSD Application Completeness | REVIEW COMPLETED |