Permit Number: TC-COM-1024-02071
Parcel: 132131850

Address:
2671 S AYALA ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1024-02071
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/13/2025 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1024-02071 (2671 S AYALA ST TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. The circuit designations on the electrical schematic do not correspond to the provided Panel Schedule.
2. Designate the circuit number, that corresponds to the panel schedule, at the location of each light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov