Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-1024-02069
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/13/2024 | PDSD Application Completeness | REQUIRES RESUBMIT | Your resubmittal is incomplete. You have not provided a comment response letter addressing the Reviewers comments (Commercial Electrical • Daniel Santa Cruz Overall Comments: Please address the electrical plan review comments and provide a written response. 1 The main electrical service panels listing has been compromised by utilizing a back-fed Main Circuit Breaker on the panel buss. Also the factory installed Main Circuit Breaker has been removed from the factory installed location and the circuit breakers appear to be of mixed manufacturers. Provide intact listed service equipment as required per NEC articles 110.3 and 230.66. 2 Revise the permit as necessary. Trade Permit, Service upgrade. Provide sealed plans as this is considered a commercial project. Ref; 2018 IBC section 107.2, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.) Please resubmit the Construction Plans along with a comment response letter. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf Please feel free to contact me if you have any questions or concerns regarding these comments. Thank you - Doris Benoit 520.633.9084 Doris.Benoit@Tucsonaz.gov |