Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2024 Site Engineering APPROVED
11/21/2024 Water - PDSD APPROVED
11/21/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 11/13/2024 12:11:24 AM
1. ENGINEER REQUIRED: The Arizona Revised Statutes ARS § 32-144 requires that a registered design professional be engaged for certain types of work. If the Building Official determines that a remodel or tenant improvement poses a significant impact to the existing structure, a structural engineer is required to sign off on the proposed work. A signed and sealed letter from a structural engineer is requested due to the following modifications to the existing structure:
i. The addition of (4) new rooftop mechanical units exceeding 300 lb. Refer to the Mechanical Floor Plan, Sheet m1. The requested letter must state the current building code and indicate that the existing roof has been evaluated for the proposed loads. If any modifications to the existing framing are required to reinforce the roof,
a structural detail must be provided.
ii. The addition of at least (1) new opening in an existing load-bearing wall. Refer to the West Elevation on Sheet a5. Please specify a new header size to be installed over the proposed opening and provide a structural detail as needed.
2. GSN - STATEMENT OF SPECIAL INSPECTIONS: The submitted Statement of Special Inspections on Sheet GSN appears to be incomplete. The scope of this project include installation of new poured-concrete footings and structural
steel columns. Please modify the Statement of Special Inspections to include the minimum inspections required by the 2018 IBC Chapter 1704. If the Registered Design Professional is requesting that the required inspections be waived,
approval from the Building Official will be required. Please submit this request in writing with the revised construction documents.
3. S1 - MISSING INFORMATION, CONCRETE FOOTINGS: The Structural Foundation Plan indicates locations for two new concrete spread footings supporting steel columns. Please add a callout to specify the minimum steel required to
reinforce these footings.
4. S1 - MISSING INFORMATION, STEEL CONNECTIONS: The Structural Foundation Plan indicates two new HSS steel columns. The structural general notes to not provide any material specifications for structural steel, bolts or welding.
Please provide additional information on the structural steel, including base plate sizes and anchorage, HSS steel material grade, miscellaneous steel material grade (plates, angles, etc) and a structural steel-to-glulam detail.
5. A1 - MISSING INFORMATION, HANDRAIL DESIGN: The Architectural Floor Plan a1, Keynote 4 indicates a proposed handrail/guardrail to be installed on the new platform. This is considered a structural item, and will require a design.
Please update the plans to state the minimum design loads for railings per the 2018 IBC Table 1607.1. Provide structural sizes and spacings for railing posts, top bars, and post anchorages (base plates and fasteners).




Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 11/2/2024 1:42:22 AM





Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Approved
Reason:
Date Completed : 11/11/2024 1:18:07 PM




Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Denied
Reason:
Date Completed : 11/4/2024 11:14:38 AM
1. E1 specifications or drawings (E4, preferred) need to call out for tamper resistant receptacles as per NEC 210.52.
2. E3 need to show an exit sign(s) for warming kitchen per IBC 1013.







Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Denied
Reason:
Date Completed : 11/3/2024 9:59:17 PM
First Plumbing Review:
1). Plan Pages P1 & P4: The 2" floor sink and 2" drain branch are undersized specifically at the 3 compartment sink. Upsize floor sink & drain branch to at least 3" to be able handle the load of all 3 sink bins being drained simultaneously without
splashing or flooding per -2018 IPC 802.4.1
2). Plan Page P1: Grease waste exit at building needs a 2 way cleanout at building. Add building cleanout on grease line Per - 2018 IPC 708.1.3
11/15/2024 Fire New Construction REQUIRES RESUBMIT -Sheet X1.1 indicates you are installing fire sprinklers. Please review IFC 903.2.1.3. Fire sprinklers are not required per the IFC however you can install if wanted.
john.vincent@tucsonaz.gov
5203495581
11/19/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
TC-COM-1024-02057
5740 E 22ND ST. – C-1
TI - Religious Use: ( 1st Review)

TRANSMITTAL: November 19, 2024
This site is located in the C-1 zone (4.7.20 ). Religious Use is an allowed use in the zone (UDC Table 4.8-4), subject to Use Specific Standard 4.9.13.O.

1. As this is a change of use either clearly demonstrate that the vehicle parking requirements are met for the religious use or review UDC Article 3.3.3.H and provide all required documentation to allow Article 3.3.3.H to be used for this use.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.