Permit Number: TC-COM-1024-02057
Parcel: 131090090

Address:
5740 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - TC-COM-1024-02057
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2025 Commercial Building Standard APPROVED Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Approved
Reason:
Date Completed : 5/9/2025 10:50:43 AM


Building(B) Reviewer
Kimiyoshi Shimabukuro
kshimabukuro@safebuilt.com
Approved
Reason:
Date Completed : 5/3/2025 8:06:02 PM
05/12/2025 Commercial Electrical Standard APPROVED Electrical(E) Reviewer
Ron Ross
rross@safebuilt.com
Approved
Reason:
Date Completed : 5/5/2025 8:54:40 AM
05/12/2025 Commercial Plumbing Standard APPROVED Plumbing(P) Reviewer
Perry Hendershott
phendershott@safebuilt.com
Approved
Reason:
Date Completed : 5/4/2025 11:45:57 PM
Revised Plumbing Review: OK
05/28/2025 Site Engineering Standard APPROVED
05/27/2025 Site Zoning Standard APPROVED
05/22/2025 Water - PDSD Standard APPROVED
05/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/12/2025 Commercial Mechanical Standard REQUIRES RESUBMIT Mechanical(M) Reviewer
Jorge Valido
jvalido@safebuilt.com
Denied
Reason:
Date Completed : 5/7/2025 4:05:11 PM
1. General - No Mechanical revisions noted on Revision Narrative letter. See resubmittal directions below. - 2018 IECC
Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction
documents.
RESUBMITTAL DIRECTIONS:
• All corrections must be clouded, delta numbered, with a brief explanation within the plan sheet or the title block of the
sheet. For corrections or revision to whole plan sheets, you need only cloud the sheet number and provide the delta
identification number, with a brief explanation of the change(s).
• As part of the resubmittal, please collate all revised sheets into the electronic document (PDF) and submit a complete
and full plan set. We cannot accept individual sheets in response to review comments, since the entire plan set is
required for approval and permitting.
• Please include with the resubmittal a separate response narrative, which is numbered or itemized to correspond to
each of the noted plan review comments items.
• This response narrative must clearly address how each issue was corrected or resolved and indicate where the
information may be found within the construction documents. The response narrative must be typewritten, on a
letterhead noting the project name, with the Permit Application Number. Failure to provide this response narrative may
result in review delays or rejection of the resubmittal.
• Once all electronic construction documents (plan sheets, energy compliance certificates, reports, calculations, etc.)
have been revised according to the above directions. Please resubmit the complete revised plan set with a separate
copy of response narrative PDF through the municipality to complete the review.
• Review of revised construction documents in response to this letter may take upwards of 5 (five) business days,
depending on the size of the project and the volume of plans in queue at time of resubmittal.
05/15/2025 Fire New Construction Standard REVIEW COMPLETED
05/01/2025 PDSD Application Completeness Express REVIEW COMPLETED