Permit Number: TC-COM-1024-02045
Parcel: 12402130A

Address:
950 N CHERRY AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-COM-1024-02045
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/31/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Provide manufactures cut sheets highlighting the model and specifications of the level 2 chargers proposed for this project.

2 Ref; Plan Sheet E-601.

2a. The ‘ELECTRICAL LOAD for EV’ box shows types ‘A’ and types ‘B’ chargers with different KWh ratings. The panel schedule for the NEW panel ‘EV’ only shows EV chargers rated at 3.6KW? Please clarify.

2b. The ‘ELECTRICAL LOAD for EV’ box indicates the Level 2 EV chargers are 208/120 volt, 3 phase, 4W configuration. Why does the panel schedule ‘EV’ show a 3.6KW single phase load with a #8 wire only with a – for the load and a – for the CB? Please clarify.

2c. Please verify all the loads are shown for the existing SES. If not, revise it to show all existing and new. Include total load calculations for the existing SES.

3 Ref; Plan Sheet ES101. (Site Plan)

3a. Identify the EV charging stations on the site plan and correlate with the panel schedule for panel ‘EV’.

3b. Identify all conduit, conductor sizes and types for all feeders and branch circuits in the site plan.

3c. What does (E)2 represent? If its Panel #2, please indicate.

3d. Show the location of (E)‘MS1’ on the site plan.

Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.