Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.4

Permit Number - TC-COM-1024-02044
Review Name: COMMERCIAL REVIEW - LIMITED v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2025 Commercial Plumbing APPROVED
02/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/26/2025 Water - PDSD REQUIRES RESUBMIT The revised calculations are partially correct. You need to use the new pressure remaining for pipe loss to determine the allowable pressure drop per 100 feet of pipe and verify that the selected pipe sizes are correct. Note: a backflow preventer (e.g. a reduced pressure zone backflow prevention assembly, ASSE 1013) is not the same as a backwater valve. A backwater valve is used only in drain and sewer applications: correct keynote 13/P101. [Initial comment: Correct the water calculations to include the pressure drop through the backflow preventer.]