Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-1024-02044
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/05/2025 | Commercial Building | APPROVED | |||
| 02/05/2025 | Commercial Electrical | APPROVED | |||
| 02/05/2025 | Commercial Mechanical | APPROVED | |||
| 02/05/2025 | Commercial Plumbing | APPROVED | 1. Approved as Noted See P101 2. Sheet P101 Provide expansion tank at water heater per IPC 2903.4.1 |
||
| 02/10/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/10/2025 | Water - PDSD | REQUIRES RESUBMIT | 1. Provide the size and serial number of the water meter serving this address, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018. 2. Correct the water calculations to include the pressure drop through the backflow preventer. |
||
| 02/04/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 01/30/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |