Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.1
Permit Number - TC-COM-1024-02044
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/08/2024 | Site Engineering | APPROVED | |||
11/19/2024 | Site Zoning | APPROVED | |||
11/21/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/11/2024 | Commercial Building | REQUIRES RESUBMIT | For questions please contact Ed Kulik: EKulik@willdan.com 1. Sheet 1 Show the occupancy of adjoining building/ suites. Show the Accessible access from the parking lot to the new construction. 2. Sheet 1 I need the following information 1. Type of construction Building Structure. 2. Occupancy Type. 3. Occupant Load. 4. Is there a existing fire sprinkler system. 3. Sheet 2 Provide the proper strike side clearance per ANSI 117.1 4. Sheet 4 Provide information on the ceiling. How tall are the walls going to be? How will you support the top of walls? Provide detail showing wall attachment. 5. Sheet 5 Remove items that do not pertain to this permit. This is not a IRC project 6. Sheet 7 Provide a list of the codes currently adopted by La Paz County. 7. Sheet 7 Remove all references to the IRC, this review is based on the 2018 IBC, 2017 NEC. |
||
11/11/2024 | Commercial Electrical | REQUIRES RESUBMIT | 1. Sheet 5 Provide 3rd party listing on the Hexagon Lighting | ||
11/11/2024 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Sheet 8 Complete mechanical plans for plan review on 2nd submittal. | ||
11/11/2024 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Sheet 3 Provide detail for the slab repair from the plumbing trench. Per the IBC 2. Sheet 6 Provide clean outs based on the 2018 Plumbing Code 3. Sheet 6 Provide a Accessible Restroom per ANSI 117. Show enlarged view of restroom with dimensions for all accessible required items. |
||
11/12/2024 | Fire New Construction | REQUIRES RESUBMIT | Address Willdan comments. questions: patricia.shelton@tucsonaz.gov |
||
11/21/2024 | Water - PDSD | REQUIRES RESUBMIT | Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. | ||