Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.2
Permit Number - TC-COM-1024-02040
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/21/2024 | Commercial Building | APPROVED | |||
12/10/2024 | Site Zoning | APPROVED | |||
12/10/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
11/29/2024 | Fire New Construction | REQUIRES RESUBMIT | -Per IFC 903.2.9, Fire sprinklers are required for S1 occupancies with a fire area that exceeds 12000sqft. The building is greater than 12000 sqft. Provide occupancy types of adjacent suites and/or fire separation information to determine if your suite is a separate fire area per IBC 707.3.10 john.vincent@tucsonaz.gov 5203495581 |
||
11/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
12/02/2024 | Site Engineering | REVIEW COMPLETED |