Permit Number: TC-COM-1024-02040
Parcel: 12415005A

Address:
830 E 16TH ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-1024-02040
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2024 Commercial Building APPROVED
12/10/2024 Site Zoning APPROVED
12/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/29/2024 Fire New Construction REQUIRES RESUBMIT -Per IFC 903.2.9, Fire sprinklers are required for S1 occupancies with a fire area that exceeds 12000sqft. The building is greater than 12000 sqft. Provide occupancy types of adjacent suites and/or fire separation information to determine if your suite is a separate fire area per IBC 707.3.10
john.vincent@tucsonaz.gov
5203495581
11/15/2024 PDSD Application Completeness Express REVIEW COMPLETED
12/02/2024 Site Engineering REVIEW COMPLETED