Permit Number: TC-COM-1024-02039
Parcel: 11310099A

Address:
2611 N WARREN AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1024-02039
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/19/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/04/2024 Commercial Building REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Building Review comments were resolved. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.
1. Please amend plans to provide code analysis for building on code data sheet. IBC 107.2.1
a. Each building’s primary occupancy classification is shown. IBC 302.1
b. Building’ construction type on a code data sheet. IBC 602.1
c. Occupant load IBC 1004.5
2. Please amend plans to provide list of the year and name of the adopted applicable codes from the adopting ordinance. IBC 107.2.1
3. Please provide a means of egress or life safety plan showing the path of travel from the building and the total travel distance. IBC 107.2.1 Please include the existing building to show how the new configuration affects egress. IBC 107.2.1
4. Please show the required 10” kick plate at the bottom of doors and gates. 2009 ICC A117.1 Section 404
5. Please provide a list the required special inspections.
6. Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B
7. completed with the next submittal. IBC 107.1 SI form link:
8. https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
11/04/2024 Fire New Construction REQUIRES RESUBMIT -Include code analysis for building. Include whether or not the building has fire sprinklers.
john.vincent@tucsonaz.gov
5203495581
11/12/2024 Site Engineering REQUIRES RESUBMIT TC-COM-1024-02039
2611 N WARREN AV

Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. The Administrative Manual can be found at:
https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes-and-Plans/Zoning-Code#section-1.

Chris Arrington
chris.arrington@tucsonaz.gov
11/19/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-COM-1024-02039
2611 N WARREN AV. - R-2
Demolition and renovation of existing courtyard space (1st Review)

TRANSMITTAL DATE: ‎November 19, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-2 zone (UDC 4.7.9). Medical Service: Extended Healthcare is a permitted use in the zone (UDC Table 4.8-2) subject to Zoning Examiner Special Exception Procedure, Section 3.4.3 and Use Specific Standards 4.9.4.O.2 and 4.9.4.P.1, 2.a, 3, & .4.

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
10/25/2024 PDSD Application Completeness Express REVIEW COMPLETED