Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.5
Permit Number - TC-COM-1024-02034
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.5
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/19/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/19/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Submit a complete set of documents that show the location of the equipment being replaced, the required air flowrates, specifications/cut sheets for the equipment being replaced, and consistent identification tags for the equipment. [Initial comment: Provide copies of the drawings used to install the equipment that is to be replaced to verify that the replacement equipment will result in proper operation of the kitchen exhaust systems. Reference: Section 107.2.1, IBC 2018.] | ||
11/14/2024 | PDSD Application Completeness | REVIEW COMPLETED |