Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TC-COM-1024-02032
Parcel: 109224450

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.3

Permit Number - TC-COM-1024-02032
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2024 Commercial Electrical APPROVED
12/30/2024 Commercial Mechanical APPROVED
12/31/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/30/2024 Commercial Plumbing REQUIRES RESUBMIT The maximum piping length for a ½” supply to a lavatory faucet in a public restroom is 2 feet, not 43 feet. Reference: Table C404.5.1, IECC 2018. [Initial comment: Verify that the distance from the hot water source (i.e., the recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]
12/31/2024 Fire New Construction REQUIRES RESUBMIT Based on the information provided regarding the O2 Dewars, the MAQ from IFC 2018, 5003.1.1(1) has been exceeded. Please update quantities to meet the allowable.
Questions: patricia.shelton@tucsonaz.gov
12/15/2024 PDSD Application Completeness Express REVIEW COMPLETED