Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-1024-02032
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/30/2024 | Commercial Electrical | APPROVED | |||
| 12/30/2024 | Commercial Mechanical | APPROVED | |||
| 12/31/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/30/2024 | Commercial Plumbing | REQUIRES RESUBMIT | The maximum piping length for a ½” supply to a lavatory faucet in a public restroom is 2 feet, not 43 feet. Reference: Table C404.5.1, IECC 2018. [Initial comment: Verify that the distance from the hot water source (i.e., the recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] | ||
| 12/31/2024 | Fire New Construction | REQUIRES RESUBMIT | Based on the information provided regarding the O2 Dewars, the MAQ from IFC 2018, 5003.1.1(1) has been exceeded. Please update quantities to meet the allowable. Questions: patricia.shelton@tucsonaz.gov |
||
| 12/15/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |