| 01/29/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/28/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Assuming that you are considering the southern restroom as “private”, show the location of the required second restroom. [Initial comment: Verify that the distance from the hot water source (i.e., the recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.] | ||
| 01/29/2025 | Fire New Construction | REVIEW COMPLETED | |||