Permit Number: TC-COM-1024-02032
Parcel: 109224450

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.2

Permit Number - TC-COM-1024-02032
Review Name: COMMERCIAL REVIEW - LIMITED v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/08/2024 Commercial Building APPROVED
11/14/2024 Site Engineering APPROVED
11/21/2024 Site Zoning APPROVED
11/13/2024 Water - PDSD APPROVED
11/21/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/12/2024 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

1 Please provide for Tamper Resistant Receptacles as required per NEC 406.12.

2 Provide for compliance of branch circuits in Patient Care and or Treatment areas per NEC 517.13.

3 Provide complete compliance with the 2018 IECC for the lighting. Comcheck Certificate is acceptable

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson Outdoor Lighting Code, City of Tucson Commercial Plan Submittal Requirements.
11/13/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Provide the volume of liquid oxygen stored in the Dewars. Reference: Section 107.2.1, IBC 2018, Section 502.9.3, IMC 2018, and Sections 105.6.10, 5003.1.4, 5306.2.2, and 6303.1.1.3, IFC 2018.
2. Show how the oxygen will be delivered to the hyperbaric chambers. Reference: Section 107.2.1, IBC 2018.
3. Provide the heating/cooling loads for the suite determined by the Carrier HAP program. Reference: Section C403.2, IECC 2018.
4. The minimum ARI efficiency for single-package heat pumps <65,000 BTUH capacity is 14 SEER. Reference: Table C403.3.3.2 (2), IECC 2018.
5. Clarify the amount of OSA provided for the toilet rooms (and washer/dryer room). See 5/M100.
11/13/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Provide shower valves that comply with the requirements of Section 412.3, IPC 2018.
2. Faucets serving lavatories in all buildings other than R3 occupancies, individual units in R2 occupancies, or International Residential Code structures shall be automatic faucets dispensing a maximum of 0.25 gallons per cycle. The cycle time shall not be less than ten-seconds for accessibility. Faucets delivering “no more than ½ gallon of water per minute” are not an option for lavatory faucets. Reference: Section 419.6, IPC 2018 as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. If the shower does not have a prefabricated receptor, provide details to show that the construction of the receptor complies with the requirements of Section 421.5, IPC 2018.
4. Verify that the distance from the hot water source (i.e., the recirculating hot water loop) to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.
11/14/2024 Fire New Construction REVIEW COMPLETED
10/29/2024 PDSD Application Completeness Express REVIEW COMPLETED