Permit Number: TC-COM-1024-02001
Parcel: 14026038C

Address:
2510 E DREXEL RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1024-02001
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/16/2024 Commercial Electrical REQUIRES RESUBMIT
12/16/2024 Commercial Mechanical REQUIRES RESUBMIT 1. Sheet G0.0 All documents and files are to be provided at each submittal. Solis report and structural calculations were missing along with other AHJ documents. 2018 IBC 107.2.1 (BM)
2. Sheet S1 Adopted Building Code for City of Tucson is 2018 IBC, will need to correct on structural plan sheet and structural calculations. 2018 IBC 107.2.1 (BM)
12/16/2024 Commercial Plumbing REQUIRES RESUBMIT 1. Sheet P3.0 Note for backflow prevention should reference 2018 IPC as adopted code per City of Tucson. (BM)
2. not addressed. Still identifies 2021 IPC as adopted per City of Tucson
12/16/2024 Commercial Structural REQUIRES RESUBMIT Sheet G0.0 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM)

1. Sheet S1 Provide completed special inspection form for review to include items listed per structural notes and soil report. Incomplete 2018 section 1705 (BM)
2. Form provided has no signature, inspector information or registrant seal on form. Will need to be noted by AHJ to provide information at later date.
01/07/2025 Site Engineering REQUIRES RESUBMIT 1. The associated development package TD-DEV-0624-00187 must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
01/03/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Ramiro Olivarez
Planner, Zoning Review Section

PROJECT: TC-COM-1024-02001
2510 E DREXEL RD TUCSON, AZ 85706 – P-I Zoning
New Commercial Building, Dutch Bros Coffee (1st Review)

TRANSMITTAL DATE: 1/3/2024

This site is located in the P-I zone (UDC 4.7.28).

COMMENTS: Please resubmit revised drawings and a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. Comment: Zoning has reviewed the building plans but cannot approve them until Development Package TD-DEV-0624-00187 has been approved.
2. Previous Comment 2 still applies: Per UDC 7.4.6.E.2., the minimum canopy clearance is 15 ft. Sheet A6.0 shows a dimensioned canopy height of 10’6”. Correct the canopy height to meet the minimum clearance.

Follow up to Comment 2: Per UDC 7.4.6.E.2., the minimum canopy clearance is 15 ft. Sheet A6.0 shows a dimensioned canopy or the “Metal Awning” in the drive through at a height of 10’6”. Correct the canopy height to meet the minimum clearance.

3. Comment: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the plans to ensure consistency with the DP.
4. Comment: Additional comments may be forthcoming on the next review based on the proposed use and applicable use specific standards.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected Building Plans.

If you have any questions about this transmittal, please contact Ramiro Olivarez Ramiro.Olivarez@tucsonaz.gov