Permit Number: TC-COM-1024-01993
Parcel: 10824011A

Address:
2450 E RIVER RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - LIMITED v.1

Permit Number - TC-COM-1024-01993
Review Name: COMMERCIAL REVIEW - LIMITED v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/12/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/31/2024 Commercial Building REQUIRES RESUBMIT Sheet CS-1 For questions in regards to plan review comments, please contact Bill McClellan by email at bmcclellan@willdan.com or cell (928)580-3179. All applicable comments followed by the initials (BM)
1. Sheet CS-1 Plywood web joists are identified in structural notes on sheet S1.1 to be deferred, will need to note as a deferral. 2018 IBC 107.3.4.1 (BM)
2. Sheet CS.2 Identify code review and new egress plan for new addition and remodel section. Not clear on plans. 2018 IBC Chapter 10 (BM)
3. Sheet CS.2 Code review Item M identifies 2 HR rated exterior walls, building plan for new addition does not identify rated wall system. Clarify 2018 IBC 107.2.1 (BM)
4. Sheet A.2 Door D213 shall be of the pivoted or side-hinged swinging type for doors in path of travel for egress unless exception (9) is applicable. Clarify 2018 IBC 1010.1.2 (BM)
5. Sheet A.8 Provide for review, door lock and latch data at new doors to comply with ADA & egress per 2018 IBC 1010.1.9.1 & 1010.1.9.4. Not clear, only item number provided (BM)
6. Sheet A1.2 Provide for review, additional details and notes for ACT ceiling installation to include wall angle detail and light and mechanical diffuser supports. Incomplete. 2018 IBC 107.2.1 (BM)
7. Sheet S1.0 Provide for review the soils report identified in note #1 in the foundations section. Incomplete 2018 IBC 107.2.1 (BM)
8. Sheet S1.1 Provide structural calculations for review for foundation, CMU walls , steel stud walls, shear walls and joists. Did not identify in plan set. 2018 IBC 107.2.1 (BM)
9. Sheet S1.2 Will need to provide completed special inspection form for items identified on plans. Incomplete . 2018 IBC 1705 (BM)
10. Sheet S2.0 Detail 114 identified is not provided on plan sheet S3.1. Clarify 2018 IBC 107.2.1 (BM)
11. Sheet X-000 Veritas plan sheets X-000 - X-300 do not have a Arizona registrant seal on pages, Clarify 2018 IBC 107.1 (BM)
12. Sheet XS-001 ( Veritas Plans ) Provide complete special inspection form for items identified in special inspection section per 2018 IBC 1705. (BM)
10/31/2024 Commercial Electrical REQUIRES RESUBMIT 1. Sheet E4.0 One line Diagram Feeders schedule does not identify feeders to 60A disconnect from bussed gutter. Clarify 2018 IBC 1078.2.1 (BM)
2. Sheet E4.0 Branch Panel L1 data identifies 30A main rating and main breaker. Clarify 2018 IBC 107.2.1 (BM)
10/31/2024 Commercial Mechanical REQUIRES RESUBMIT
10/31/2024 Commercial Plumbing REQUIRES RESUBMIT
11/04/2024 Site Engineering REQUIRES RESUBMIT The associated development package TD-DEV-1024-00279 must be approved before this building permit can be approved.

Mike Ortiz
michael.ortiz@tucsonaz.gov
11/12/2024 Site Zoning REQUIRES RESUBMIT FROM: Bobby Parsons - Planner
PDSD Zoning Review Section

PROJECT: TC-COM-1024-01993 (Medical Services Outpatient)
New addition to existing medical office (1st review)
2450 E River Road Tucson, AZ 85718 (O-3)

TRANSMITTAL DATE: 11/12/2024

DUE DATE: 11/4/2024

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

01. COMMENT: Zoning has conducted a cursory review of the building permit plan set. Zoning cannot approve the building permit plan set until the development package has been reviewed and approved. Zoning will review the building plans on the next submittal and confirm compliance with the approved development package.

For questions regarding Zoning comments, please contact me at Robert.Parsons@tucsonaz.gov (520) 837-4977.
10/31/2024 Water - PDSD REQUIRES RESUBMIT
10/28/2024 Fire New Construction REVIEW COMPLETED
10/21/2024 PDSD Application Completeness Express REVIEW COMPLETED